Venting is a part of an installation where a shortcut is not just inefficient, it can be dangerous. Your vent carries combustion gases out of your home, and it has to clear windows, doors, decks, and your gas meter by measured distances that exist for a reason. Honest Fix vents every system to a written standard: correct clearances, sealed the right way for the surface, and sloped and sized to the manufacturer's spec. This page is that standard, published in full, so you can hold any contractor to it. Ours included.

Published from our Installation Handbook · Reviewed by Alex Largent · 100% satisfaction, no exceptions

THE HONEST FIX VENTING STANDARD

What Safe Venting Has to Get Right

Your vent is the path combustion gases take to leave your home. Every rule on this page exists so those gases go out and stay out, and so your vent survives wind, weather, and an Upper Ohio Valley winter without pulling loose or leaking. Here is the standard, including the clearance tables that usually stay inside an installation manual. These are the clearances Honest Fix holds on every venting job. Where the manufacturer's instructions for your appliance or your local code ask for more, that is what gets built.

Clearances to openings and the meter

A vent termination keeps a measured distance from anything it could contaminate or endanger: windows and doors, closed windows, soffits, inside and outside corners, air inlets, sidewalks, decks, and your electric and gas meters. The distance depends on whether your system is direct vent, and on the appliance's input rating. The table below is the full list Honest Fix holds.

Vent termination clearances

Clearance from the vent termination toHonest Fix minimum
Grade, or the surface of a porch, balcony, or deck, below it1 foot
A window or door that can be openedDirect vent: 1 foot in every direction. Other vents: 1 foot above, 4 feet below or to the side
A permanently closed window1 foot
A ventilated soffit within 2 feet horizontally of the vent centerline, measured vertically2 feet
An unventilated soffit2 feet
An outside corner2 feet
An inside corner3 feet
An electric or gas meter, to each side of its centerline and above it3 feet. Where 3 feet to either side cannot be held, the termination sits 15 feet above the meter
A non-mechanical air supply inlet, or another appliance's combustion air inletDirect vent: 1 foot for an appliance over 10,000 and up to 100,000 BTUH, 3 feet over 100,000 BTUH. Other vents: 4 feet below or to the side, 1 foot above
A mechanical air supply inlet3 feet above it, if within 10 feet horizontally
A paved sidewalk or driveway, below it7 feet
The underside of a porch, balcony, or deck1 foot if the deck is fully open on at least 2 sides, otherwise 2 feet

Where the manufacturer's instructions for your appliance or your local code ask for more, that is what gets built.

Clearance to combustibles

Every vent type keeps a set distance from anything that can burn, and each one has its own rule for terminating through a roof. Single-wall, Type B, Type A, and direct-vent pipe each get their own clearance. The table below lists each one.

Clearance to combustibles by vent type

Vent typeHonest Fix minimum to anything combustible
Single-wall vent6 inches. Never terminates through a roof
Type B double-wall vent1 inch. Terminates at least 2 feet above the roof
Type A vent2 inches. Terminates at least 2 feet above the roof, within 10 feet horizontally
Direct-vent (DV) pipe1 inch. Terminates at least 2 feet above the roof

Where the manufacturer's instructions for your appliance or your local code ask for more, that is what gets built.

Sealed correctly for the surface

The sealant is matched to what it seals. Asphalt shingle flashings and nail holes are sealed with Blackjack asphalt shingle sealer or an equivalent product, never silicone or Vulkem, which will not bond to shingle. B-vent storm collars and metal-to-metal flashings are sealed with Vulkem or an equivalent product. A hole cut in siding for a sidewall termination is sealed with caulk or thumb gum. Storm collars are always sealed, whatever flashing is used.

Built for wind and snow

Where a concentric vent kit is used, or where venting has to stand more than two feet above the roofline, your technician uses a three-inch B-vent flashing and storm collar for rigidity in high wind, instead of a no-caulk flashing. A Type B vent terminates at least two feet above the roofline. A concentric kit clears the expected snow level by twelve inches, and with the four inches of snow Honest Fix plans for here, that means sixteen inches above the roofline at the lowest point.

Sloped and sized to spec

Every vent has a designed slope, for draft, for condensate, or both, and your technician takes it from the manufacturer's literature for that specific appliance, never from habit. Every gas appliance also has a maximum equivalent vent length, and each elbow counts against it, so the run is measured and adjusted for the number and type of elbows. Long-radius elbows only. Mitered and short-radius elbows are not used.

WHY THIS ONE MATTERS HERE

In an Upper Ohio Valley Winter, a Vent Has to Survive the Weather

Ridge-top wind and a real snow load are part of a normal winter here, not edge cases. A vent that would hold up in a milder, flatter place can pull loose or get buried in ours, and a blocked or leaking vent is a safety problem in your home, not just a comfort one.

Too close to a window or door

A termination set short of its clearance can let combustion gases be drawn back into your home through the nearest opening. The termination clearances on this page are what keep that from happening.

The wrong sealant on the flashing

Silicone on an asphalt shingle will not bond, so the seal fails and your roof leaks around the vent. Each surface gets its matched sealant, or the leak is a matter of when, not if.

Set too low for the snow

A termination that does not clear the snow line can be buried or blocked in a hard winter, and a blocked vent shuts your system down at best. That is why a concentric kit clears your roofline by sixteen inches here.

Too many elbows, too long a run

Every elbow shortens how far a vent can run. A run that ignores the maximum equivalent length, or leans on short-radius elbows, will not draft the way the manufacturer designed it to.

Field conditions. Final installation details may vary based on manufacturer requirements, local code, home conditions, equipment model, safety constraints, and the written scope of work. Where the manufacturer's instructions and this standard disagree, the manufacturer's instructions win, and your technician follows them. 

FURNACE VENTING

Common Questions

Why does my furnace vent have to be so far from my windows?

What is the white PVC pipe running out the side of my house?

Can a furnace be vented through the roof, or does it have to go out the side?

My vent terminates near my deck. Is that a problem?

Why does the vent need to stick up so far above my roof?

Can a vent run be too long or have too many elbows?

How do I know my system was vented correctly?